Multicore Flat Cables
|

|
The PVC insulated and sheathed multicore flat cables are used for giving electrical connection to the submersible pump motors. These are manufactured keeping in mind the severe, tough and difficult conditions in which they have to operate. The slot available in the tube well being narrow the shape of the cables has to be suited for such an application. These cables conform to and are marked IS 694: 1990.
Manufactured from bright-annealed 99.97% pure bare copper conductors these cables have low conductor resistance. The inner cores are insulated with a special grade PVC compound. The tough outer PVC jacket protects it from oils, greases, various chemicals and abrasions, thereby giving long life and electrical
safety.
|
| Technical Information
|
|
Working voltage |
1100 V |
|
Temperature range |
15 deg C to +70 deg C |
|
Sizes |
1.5 to 4.0 sq mm with ISI
mark 6.0 to 95 sq mm generally conforming to IS 694:1990 |
|
Color codes Cores |
Red, Yellow and
Blue
Black outer sheath
Grey sheath on specific request |
|
Specification |
IS 694:1990 |
| Packing |
500 / 1000m on drums |
Area
(Nom.)
Sq. mm |
Number / size of
wire mm |
Insulation
Thickness (Nom.) mm |
Sheath Thickness
(Nom.) mm |
Width 'W' mm |
Thickness
'H' mm |
Resistance @ 20°
C (max.) Ohm/Km |
Current carrying
capacity @ 40° C Amps. |
| 1.5 |
22/.3 |
0.6 |
0.9 |
11.0 |
5.0 |
12.10 |
14 |
| 2.5 |
36/.3 |
0.7 |
1.0 |
13.0 |
6.0 |
7.40 |
18 |
| 4.0 |
56/.3 |
0.8 |
1.0 |
15.3 |
6.7 |
4.95 |
26 |
| 6.0 |
84/.3 |
1.0 |
1.15 |
18.7 |
7.9 |
3.30 |
31 |
| 10.0 |
140/.3 |
1.0 |
1.40 |
23.7 |
9.9 |
1.91 |
42 |
| 16.0 |
226/.3 |
1.0 |
1.40 |
28.0 |
11.4 |
1.21 |
57 |
| 25.0 |
354/.3 |
1.2 |
2.0 |
35.5 |
14.7 |
0.780 |
72 |
| 35.0 |
495/.3 |
1.2 |
2.0 |
39.5 |
16.2 |
0.554 |
90 |
| 50.0 |
703/.3 |
1.4 |
2.20 |
45.5 |
18.3 |
0.386 |
115 |
| 70.0 |
360/.5 |
1.4 |
2.20 |
51.0 |
20.0 |
0.272 |
143 |
| 95.0 |
475/.5 |
1.6 |
2.40 |
60.0 |
23.5 |
0.206 |
165 |
|
 |
Note: Insulation thickness, Sheath thickness and overall dimensions given in this table are nominal values. The number of wires is approximate and strand diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per IS 8130/1984.
Guidelines for Selection of 3 Core Flat Cables
1) HP Vs Current :The full load current for submersible pump motors, 3 phase, 50 cycles, 415 ~ 425 V.
|
|
HP
|
5.0
|
7.5
|
10.0
|
12.5
|
15.0
|
17.5
|
20.0
|
25.0
|
30.0
|
35.0
|
40.0
|
45.0
|
50.0
|
55.0
|
60.0
|
65.0
|
70.0
|
75.0
|
80.0
|
|
Amp
|
7.5
|
11.0
|
14.9
|
18.9
|
22.5
|
25.2
|
28.4
|
35.6
|
42.3
|
50.4
|
58.1
|
62.1
|
67.5
|
73.8
|
81.0
|
87.3
|
93.6
|
100.8
|
108.0
|
|
2) Derating Factors : Multiply the current carrying capacity of
the cable by factors given below for various ambient temperatures.
|
|
Ambient Temperature ° C
|
30
|
35
|
40
|
45
|
50
|
|
Derating Factor |
1.09
|
1.04
|
1.00
|
0.95
|
0.77
|
|
 |
| Power and Control Cables
|| Multi
Core Flat Cables || PVC
Flexible Cables || Single
Core Flexible Cables |
| Multi Core Flexible Cables
|| Co-Axial Cables || Flame
Retardant Low Smoke Cables |
|
|