1. Rating factors for Depth of laying
| Depth Of Laying cm |
Upto 25 mm˛ |
Above 25 mm˛ Upto 300 mm˛ |
Above 300 mm˛ |
| 75 |
1.00 |
1.00 |
1.00 |
| 90 |
0.99 |
0.98 |
0.97 |
| 105 |
0.98 |
0.97 |
0.96 |
| 120 |
0.97 |
0.96 |
0.95 |
| 150 |
0.96 |
0.94 |
0.92 |
| 180 or more |
0.95 |
0.93 |
0.91 |
2. Rating factors for depth of laying (Twin and multicore cables in single way ducts)
| Depth Of Laying cm |
Rating Factor |
| 75 |
1.00 |
| 90 |
0.99 |
| 105 |
0.98 |
| 120 |
0.97 |
| 150 |
0.96 |
| 180 |
0.95 |
| 270 |
0.92 |
| 360 |
0.91 |
| 450 |
0.90 |
| 540 or more |
0.89 |
3. Rating factors for the single core cables (AC) in flat formation in air (to be applied to the corresponding ratings
for trefoil groups in air)
| Nominal Area
of conductor in mm2 |
Rating Factor |
| Upto &
including 185 |
1.07 |
| 240 |
1.10 |
| 300 |
1.08 |
| 400 |
1.04 |
| 500 |
1.00 |
| 630 |
1.00 |
4. Rating factors for variation in
Ground Temperature for cables laid direct in ground
| Ground
Temperature°C |
15 |
20 |
25 |
30 |
35 |
45 |
40 |
| Rating
Factor |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.87 |
0.79 |
5. Rating factors for variation in
Ground Temperature for cables in ducts
| Ground
Temperature°C |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
| Rating
Factor |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.87 |
0.79 |
6. Rating factors for variation in
Ground Temperature for cables in ducts-
| Air
Temperature°C |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
| Rating
Factor |
1.33 |
1.25 |
1.16 |
1.09 |
1.00 |
0.90 |
0.83 |
Note : For cables in air no
reduction in current rating is necessary provided that
1.The horizontal clearance between circuits is :
a. not less than six times the overall diameter of an individual cable and,
b. not less than the overall width of an individual circuit except that the horizontal clearance need not exceed 150 mm in any case.
2. The vertical clearance between circuits is not less than 150 mm.
3. If the number of circuits exceeds 4 ,they are installed in horizontal plane.
However ,for installation conditions other than above current rating factors incorporated in IS : 3961-Part II may please be applied.
The following points should be taken into consideration before selecting particular size & type of cable :
1.The system of power & voltage source where the cables are being used.
2.Conditions of installation at site.
3.Current carrying capacity of cable.
4.Voltage Drop of cable.
5.Short circuit capacity of cable.
6.Availability of the selected size of cable.
Short Circuit rating in K.amp for One Second Duration
| Area of Conductor
Sq.mm |
Aluminium
Conductor PVC |
Aluminium
Conductor HRPVC |
Copper Conductor
PVC |
Copper Conductor
HRPVC |
| 1.5 |
0.1126 |
0.097 |
0.169 |
0.153 |
| 2.5 |
0.1878 |
0.162 |
0.283 |
0.255 |
| 4.0 |
0.3004 |
0.259 |
0.452 |
0.406 |
| 6.0 |
0.4507 |
0.389 |
0.679 |
0.612 |
| 10.0 |
0.7512 |
0.648 |
1.132 |
1.020 |
| 16.0 |
1.200 |
1.087 |
1.810 |
1.632 |
| 25.0 |
1.870 |
1.620 |
2.830 |
2.550 |
| 35.0 |
2.620 |
2.270 |
3.960 |
3.570 |
| 50.0 |
3.750 |
3.243 |
5.660 |
5.100 |
| 70.0 |
5.250 |
4.540 |
7.920 |
7.140 |
| 95.0 |
7.130 |
6.150 |
10.750 |
9.690 |
| 120.0 |
9.000 |
7.784 |
13.580 |
13.340 |
| 150.0 |
11.260 |
9.730 |
16.980 |
15.300 |
| 185.0 |
13.890 |
12.000 |
20.940 |
18.870 |
| 240.0 |
18.020 |
15.560 |
27.160 |
24.480 |
| 300.0 |
22.530 |
19.460 |
33.960 |
30.600 |
| 400.0 |
30.040 |
25.940 |
45.280 |
40.800 |
| 500.0 |
37.560 |
32.430 |
56.600 |
51.000 |
| 630.0 |
47.320 |
40.860 |
71.310 |
64.250 |
Formula for calculating the Short
circuit current for other duration's
It = I1 / (t)0.5
It = I1 / (t)0.5
Where :-
It : Short Circuit Current for t seconds
I1 : Short Circuit Current for one second
t : Duration in Seconds
Maximum conductor temperature during short circuit is 160°C for both PVC and HRPVC cables.
|