PRODUCTS


"KAYDOUR" 1.1 KV Annealed High Conductivity Solid Copper Conductor 2.5 Sq. Mm. PVC Insulated, 
 Armoured /Unarmoured & PVC Sheathed Control Cables Conforming To IS:1554 (Part-I) Amended Upto Date    

 
No. Of Cores  Nominal thickness of Insulation mm Minimum thickness of Inner sheath mm ARMOUR Nominal thickness of Outer  sheath mm Approx. Overall diameter mm Approx. weight of cable  kg / km
Max.DC conductor resistance at 20º C Ohm/km CURRENT RATINGS
Galv. Round Steel wire Nominal Diameter mm  Galv. Flat Steel Strip Nominal thickness mm Direct in Ground Amps In Ducts Amps In Air Amps 
Unarmoured mm Armoured mm Unarmoured mm Armoured mm Unarmoured mm Armoured mm
2 0.9 0.3 1.4 - 1.8 1.8 11.6 14.8 215 504 7.28 32 27 27
0.9 0.3 1.4 - 1.8 1.8 12.2 15.4 247 560 7.28 27 24 24
4 0.9 0.3 1.4 1.8 1.8 13.1 16.3 285 625 7.28 27 24 24
5 0.9 0.3 1.4 - 1.8 1.8 14.2 17.4 370 730 7.28 27 24 24
6 0.9 0.3 1.4 - 1.8 1.8 15.2 18.4 400 820 7.28 20 18 18
7 0.9 0.3 1.4 - 1.8 1.8  15.2 18.4 410 860 7.28  20 17 17
10 0.9 0.3 0.8 2.0 2.0 19.3 21.6 580 900 7.28 18 15 15
12 0.9 0.3 0.8 2.0 2.0 19.8 22.1 650 1000 7.28 17  14 14
14 0.9 0.3 - 0.8 2.0 2.0 20.8 23.1 740 1150 7.28 16 13 13
16 0.9 0.3 0.8 2.0 2.0 21.9 24.2 840 1210 7.28 15 13 13
19 0.9 0.3 0.8 2.0 2.0 22.9 25.2 950 1400 7.28 14 12 12
24 0.9 0.3 0.8 2.0 2.0 26.6 28.9 1200 1700 7.28 13 11 11
30 0.9 0.3 - 0.8 2.0 2.2 28.1 30.8 1450 1950 7.28 12 10 10
37 0.9 0.4 - 0.8 2.2 2.2 30.8 32.9 1800 2250 7.28 11 10 10
61 0.9 0.4 - 0.8 2.2 2.4 38.1 40.6 2700 3400 7.28 9 8 8
* If required, cables can be made with standard conductor also Not covered in IS : 1554 (Part - I)1976