1.1 Kv Annealed 1.5 Sq. mm

"KAYDOUR" 1.1 KV Annealed High Conductivity Solid Copper Conductor 2.5 Sq. Mm. PVC Insulated, 
 Armoured /Unarmoured & PVC Sheathed Control Cables Conforming To IS:1554 (Part-I) Amended Upto Date    

No. Of Cores 

Nominal thickness of Insulation mm

Minimum thickness of Inner sheath mm

ARMOUR

Nominal thickness of Outer  sheath mm

Approx. Overall diameter mm

Approx. weight of cable  kg / km

Max.DC conductor resistance at 20º C Ohm/km

CURRENT RATINGS

Galv. Round Steel wire Nominal Diameter mm 

Galv. Flat Steel Strip Nominal thickness mm

Direct in Ground Amps

In Ducts Amps

In Air Amps 

Armoured mm

Armoured mm

Armoured mm

2

0.9

0.3

1.4

-

1.8

1.8

11.6

14.8

215

504

7.28

32

27

27

0.9

0.3

1.4

-

1.8

1.8

12.2

15.4

247

560

7.28

27

24

24

4

0.9

0.3

1.4

1.8

1.8

13.1

16.3

285

625

7.28

27

24

24

5

0.9

0.3

1.4

-

1.8

1.8

14.2

17.4

370

730

7.28

27

24

24

6

0.9

0.3

1.4

-

1.8

1.8

15.2

18.4

400

820

7.28

20

18

18

7

0.9

0.3

1.4

-

1.8

1.8 

15.2

18.4

410

860

7.28 

20

17

17

10

0.9

0.3

0.8

2.0

2.0

19.3

21.6

580

900

7.28

18

15

15

12

0.9

0.3

0.8

2.0

2.0

19.8

22.1

650

1000

7.28

17 

14

14

14

0.9

0.3

-

0.8

2.0

2.0

20.8

23.1

740

1150

7.28

16

13

13

16

0.9

0.3

0.8

2.0

2.0

21.9

24.2

840

1210

7.28

15

13

13

19

0.9

0.3

0.8

2.0

2.0

22.9

25.2

950

1400

7.28

14

12

12

24

0.9

0.3

0.8

2.0

2.0

26.6

28.9

1200

1700

7.28

13

11

11

30

0.9

0.3

-

0.8

2.0

2.2

28.1

30.8

1450

1950

7.28

12

10

10

37

0.9

0.4

-

0.8

2.2

2.2

30.8

32.9

1800

2250

7.28

11

10

10

61

0.9

0.4

-

0.8

2.2

2.4

38.1

40.6

2700

3400

7.28

9

8

8

* If required, cables can be made with standard conductor also Not covered in IS : 1554 (Part - I)1976

Best view : 1024 x 768 Pixels

Designed & Hosted by : MID   Promoted by : GID