1.1 Kv Annealed 1.5 Sq. mm

"KAYDOUR" 1.1 KV Annealed High Conductivity Solid Copper Conductor 1.5 Sq. Mm. PVC Insulated, Inner Sheathed, Armoured /Unarmoured & PVC Sheathed Control Cables Conforming To IS:1554 (Part-I) Amended Upto Date    
 

Nominal cross sectional area 

Sq. mm

Nominal thickness of Insulation mm

Minimum thickness of Inner sheath mm

ARMOUR

Nominal thickness of Outer  sheath mm

Approx. Overall diameter mm

Approx. weight of cable  kg / km

Max. DC conductor resistance at 20º C Ohm/km

CURRENT RATINGS

Galv. Round Steel wire Nominal Diameter mm 

Galv. Flat Steel Strip Nominal thickness mm

Direct in Ground Amps

In Ducts Amps

In Air Amps 

Unarmoured mm

Armoured mm

Unarmoured mm

Armoured mm

Unarmoured mm

Armoured mm

2

0.8

0.3

1.4

-

1.8

1.8

10.4

13.6

167

440

12.1

23

20

20

3

0.8

0.3

1.4

-

1.8

1.8

10.9

14.1

200

478

12.1

21

17

17

4

0.8

0.3

1.4

-

1.8

1.8

11.7

14.9

230

526

12.1

21

17

17

5

0.8

0.3

1.4

-

1.8

1.8

12.6

15.7

250

630

12.1

21

17

17

6

0.8

0.3

1.4

-

1.8

1.8

13.4

16.6

300

675

12.1

15

13

13

7

0.8

0.3

1.4

-

1.8

1.8

13.4

16.6

320

690

12.1

14

13

132

10

0.8

0.3

-

0.8

1.8

2.0

16.5

19.2

430

810

12.1

13

11

11

12

0.8

0.3

-

0.8

1.8

2.0

17.0

19.7

450

870

12.1

12

10

10

14

0.8

0.3

-

0.8

1.8

2.0

17.7

20.4

510

968

12.1

11

10

10

16

0.8

0.3

-

0.8

2.0

2.0

19.0

21.3

620

1068

12.1

11

9

9

19

0.8

0.3

-

0.8

2.0

2.0

19.9

22.2

660

1155

12.1

10

9

9

24

0.8

0.3

-

0.8

2.0

2.0

23.0

25.3

820

1300

12.1

9

8

8

30

0.8

0.3

-

0.8

2.0

2.0

24.2

26.5

980

1550

12.1

9

7

7

37

0.8

0.3

-

0.8

2.0

2.0

26.0

28.3

1200

1765

12.1

8

7

7

61

0.8

0.4

-

0.8

2.2

2.2

32.7

34.8

1850

2400

12.1

7

6

6

* If required, cables can be made with standard conductor also Not covered in IS : 1554 (Part - I)1976

Best view : 1024 x 768 Pixels

Designed & Hosted by : MID   Promoted by : GID